I would like to know if there is a bug in the plugin, or I am doing something wrong.

I have a Cisco 9300 series switch and I monitor environment from there.

Currently it is showing:

WARNING: Sensor 'Switch 1 - C9300-48P - Temp Inlet Sensor 0/1012' is 31 C

Environment type: other
Checking fans
fan 'Switch 1 - FAN - T1 1, Normal' status is normal instance: 1017].
fan 'Switch 1 - FAN - T1 2, Normal' status is normal instance: 1018].
fan 'Switch 1 - FAN - T1 3, Normal' status is normal instance: 1019].
fan 'Switch 1 - C9300-48P - FAN 1' status is up instance: 1017]
fan 'Switch 1 - C9300-48P - FAN 2' status is up instance: 1018]
fan 'Switch 1 - C9300-48P - FAN 3' status is up instance: 1019]
Checking power supplies
power supply 'Switch 1 - Power Supply A, Normal' status is normal instance: 1015] source: ac]
power supply 'Switch 1 - Power Supply B, NotExist' status is not present instance: 1016] source: unknown]
Checking temperatures
temperature 'Switch 1 - Inlet Temp Sensor, GREEN ' status is normal instance: 1012] value: 31 C]
temperature 'Switch 1 - Outlet Temp Sensor, GREEN ' status is normal instance: 1013] value: 36 C]
temperature 'Switch 1 - HotSpot Temp Sensor, GREEN ' status is normal instance: 1014] value: 50 C]
Checking voltages
Checking modules
module 'C9300-48P' status is ok instance: 1000]
Checking physicals
Checking sensors
sensor 'Switch 1 - C9300-48P - Temp Inlet Sensor 0' status is 'ok' instance: 1012] value: 31 celsius]
sensor 'Switch 1 - C9300-48P - Temp Outlet Sensor 1' status is 'ok' instance: 1013] value: 36 celsius]
sensor 'Switch 1 - C9300-48P - Temp Hotspot Sensor 2' status is 'ok' instance: 1014] value: 50 celsius]
sensor 'TenGigabitEthernet1/1/1 Module Temperature Sensor' status is 'ok' instance: 1129] value: 32.7 celsius]
sensor 'TenGigabitEthernet1/1/1 Supply Voltage Sensor' status is 'ok' instance: 1130] value: 3.3 voltsDC]
sensor 'TenGigabitEthernet1/1/1 Bias Current Sensor' status is 'ok' instance: 1131] value: 0.0252 amperes]
sensor 'TenGigabitEthernet1/1/1 Transmit Power Sensor' status is 'ok' instance: 1132] value: -2.9 dBm]
sensor 'TenGigabitEthernet1/1/1 Receive Power Sensor' status is 'ok' instance: 1133] value: -5.7 dBm]

My command is:

/usr/lib/nagios/plugins/centreon_plugins.pl --plugin network::cisco::standard::snmp::plugin --mode=environment --hostname=1.2.3.4 --snmp-version=2c --snmp-community=xxx --verbose --critical='sensor,1012,56' --warning='sensor,1012,46' --snmp-retries=3

Why is it still showing as warning? Should the warning and critical part syntax be something different than the above one?

 

 

Hi,

Have you tried this?

--critical='temperature,1012,56' --warning='temperature,1012,46'


bash-5.1$ /usr/lib/centreon/plugins/centreon_cisco_standard_snmp.pl --plugin network::cisco::standard::snmp::plugin --mode=environment --hostname=1.3.3.2 --snmp-username=kkk --authpassphrase=btca --authprotocol=SHA --privpassphrase=GHcjc --privprotocol=AES --snmp-version=3 --verbose --critical='temperature,1010,56' --warning='temperature,1010,46'

WARNING: Sensor 'Switch 1 - C9200L-24P-4G - Temp Inlet Sensor 0/1010' is 26 C | 'temp_Switch 1 - Inlet Temp Sensor, GREEN '=26C;0:46;0:56;; 'temp_Switch 1 - Outlet Temp Sensor, GREEN '=30C;;~:125;; 'temp_Switch 1 - HotSpot Temp Sensor, GREEN '=39C;;~:125;; 'sensor.celsius_Switch 1 - C9200L-24P-4G - Temp Outlet Sensor 1'=30C;;-9:124;; 'sensor.celsius_Switch 1 - C9200L-24P-4G - Temp Hotspot Sensor 2'=39C;;-9:124;; 'sensor.celsius_GigabitEthernet1/1/1 Module Temperature Sensor'=27.3C;;;; 'sensor.voltsDC_GigabitEthernet1/1/1 Supply Voltage Sensor'=3.2V;;;; 'sensor.amperes_GigabitEthernet1/1/1 Bias Current Sensor'=0.0191A;;;; 'sensor.dBm_GigabitEthernet1/1/1 Transmit Power Sensor'=-6dBm;;;; 'sensor.dBm_GigabitEthernet1/1/1 Receive Power Sensor'=-6.9dBm;;;; 'sensor.celsius_GigabitEthernet1/1/2 Module Temperature Sensor'=28.1C;;;; 'sensor.voltsDC_GigabitEthernet1/1/2 Supply Voltage Sensor'=3.3V;;;; 'sensor.amperes_GigabitEthernet1/1/2 Bias Current Sensor'=0.0216A;;;; 'sensor.dBm_GigabitEthernet1/1/2 Transmit Power Sensor'=-5.9dBm;;;; 'sensor.dBm_GigabitEthernet1/1/2 Receive Power Sensor'=-7.3dBm;;;; 'sensor.celsius_GigabitEthernet1/1/3 Module Temperature Sensor'=28.1C;;;; 'sensor.voltsDC_GigabitEthernet1/1/3 Supply Voltage Sensor'=3.3V;;;; 'sensor.amperes_GigabitEthernet1/1/3 Bias Current Sensor'=0.0208A;;;; 'sensor.dBm_GigabitEthernet1/1/3 Transmit Power Sensor'=-5.7dBm;;;; 'sensor.dBm_GigabitEthernet1/1/3 Receive Power Sensor'=-5.8dBm;;;; 'sensor.celsius_GigabitEthernet1/1/4 Module Temperature Sensor'=27.9C;;;; 'sensor.voltsDC_GigabitEthernet1/1/4 Supply Voltage Sensor'=3.2V;;;; 'sensor.amperes_GigabitEthernet1/1/4 Bias Current Sensor'=0.0214A;;;; 'sensor.dBm_GigabitEthernet1/1/4 Transmit Power Sensor'=-5.8dBm;;;; 'sensor.dBm_GigabitEthernet1/1/4 Receive Power Sensor'=-7.1dBm;;;; 'sensor.celsius_Switch 1 - C9200L-24P-4G - Temp Inlet Sensor 0'=26C;32:45;-9:55;; 'count_fan'=4;;;; 'count_module'=1;;;; 'count_psu'=2;;;; 'count_sensor'=23;;;; 'count_temperature'=3;;;;

Environment type: other

Checking fans

fan 'Switch 1 - FAN - T1 1, Normal' status is normal instance: 1015].

fan 'Switch 1 - FAN - T1 2, Normal' status is normal instance: 1016].

fan 'Switch 1 - C9200L-24P-4G - FAN 1' status is up instance: 1015]

fan 'Switch 1 - C9200L-24P-4G - FAN 2' status is up instance: 1016]

Checking power supplies

power supply 'Switch 1 - Power Supply A, Normal' status is normal instance: 1013] source: ac]

power supply 'Switch 1 - Power Supply B, Normal' status is normal instance: 1014] source: ac]

Checking temperatures

temperature 'Switch 1 - Inlet Temp Sensor, GREEN ' status is normal instance: 1010] value: 26 C]

temperature 'Switch 1 - Outlet Temp Sensor, GREEN ' status is normal instance: 1011] value: 30 C]

temperature 'Switch 1 - HotSpot Temp Sensor, GREEN ' status is normal instance: 1012] value: 39 C]

Checking voltages

Checking modules

module 'C9200L-24P-4G' status is ok instance: 1000]

Checking physicals

Checking sensors

sensor 'Switch 1 - C9200L-24P-4G - Temp Inlet Sensor 0' status is 'ok' instance: 1010] value: 26 celsius]

sensor 'Switch 1 - C9200L-24P-4G - Temp Outlet Sensor 1' status is 'ok' instance: 1011] value: 30 celsius]

sensor 'Switch 1 - C9200L-24P-4G - Temp Hotspot Sensor 2' status is 'ok' instance: 1012] value: 39 celsius]

sensor 'GigabitEthernet1/1/1 Module Temperature Sensor' status is 'ok' instance: 1091] value: 27.3 celsius]

sensor 'GigabitEthernet1/1/1 Supply Voltage Sensor' status is 'ok' instance: 1092] value: 3.2 voltsDC]

sensor 'GigabitEthernet1/1/1 Bias Current Sensor' status is 'ok' instance: 1093] value: 0.0191 amperes]

sensor 'GigabitEthernet1/1/1 Transmit Power Sensor' status is 'ok' instance: 1094] value: -6 dBm]

sensor 'GigabitEthernet1/1/1 Receive Power Sensor' status is 'ok' instance: 1095] value: -6.9 dBm]

sensor 'GigabitEthernet1/1/2 Module Temperature Sensor' status is 'ok' instance: 1097] value: 28.1 celsius]

sensor 'GigabitEthernet1/1/2 Supply Voltage Sensor' status is 'ok' instance: 1098] value: 3.3 voltsDC]

sensor 'GigabitEthernet1/1/2 Bias Current Sensor' status is 'ok' instance: 1099] value: 0.0216 amperes]

sensor 'GigabitEthernet1/1/2 Transmit Power Sensor' status is 'ok' instance: 1100] value: -5.9 dBm]

sensor 'GigabitEthernet1/1/2 Receive Power Sensor' status is 'ok' instance: 1101] value: -7.3 dBm]

sensor 'GigabitEthernet1/1/3 Module Temperature Sensor' status is 'ok' instance: 1103] value: 28.1 celsius]

sensor 'GigabitEthernet1/1/3 Supply Voltage Sensor' status is 'ok' instance: 1104] value: 3.3 voltsDC]

sensor 'GigabitEthernet1/1/3 Bias Current Sensor' status is 'ok' instance: 1105] value: 0.0208 amperes]

sensor 'GigabitEthernet1/1/3 Transmit Power Sensor' status is 'ok' instance: 1106] value: -5.7 dBm]

sensor 'GigabitEthernet1/1/3 Receive Power Sensor' status is 'ok' instance: 1107] value: -5.8 dBm]

sensor 'GigabitEthernet1/1/4 Module Temperature Sensor' status is 'ok' instance: 1109] value: 27.9 celsius]

sensor 'GigabitEthernet1/1/4 Supply Voltage Sensor' status is 'ok' instance: 1110] value: 3.2 voltsDC]

sensor 'GigabitEthernet1/1/4 Bias Current Sensor' status is 'ok' instance: 1111] value: 0.0214 amperes]

sensor 'GigabitEthernet1/1/4 Transmit Power Sensor' status is 'ok' instance: 1112] value: -5.8 dBm]

sensor 'GigabitEthernet1/1/4 Receive Power Sensor' status is 'ok' instance: 1113] value: -7.1 dBm]


Can you run the same command with the --debug option please?


bash-5.1$ /usr/lib/centreon/plugins/centreon_cisco_standard_snmp.pl --plugin network::cisco::standard::snmp::plugin --mode=environment --hostname=1.3.3.5 --snmp-version=2c --snmp-community='public' --verbose --snmp-retries=3 --critical='temperature,1012,56' --warning='temperature,1012,46' --debug

WARNING: Sensor 'Switch 1 - C9300-24P - Temp Inlet Sensor 0/1012' is 30 C | 'temp_Switch 1 - Inlet Temp Sensor, GREEN '=30C;0:46;0:56;; 'temp_Switch 1 - Outlet Temp Sensor, GREEN '=34C;;~:125;; 'temp_Switch 1 - HotSpot Temp Sensor, GREEN '=47C;;~:125;; 'sensor.celsius_Switch 1 - C9300-24P - Temp Outlet Sensor 1'=34C;;-9:124;; 'sensor.celsius_Switch 1 - C9300-24P - Temp Hotspot Sensor 2'=47C;;-9:124;; 'sensor.celsius_GigabitEthernet1/1/1 Module Temperature Sensor'=29.7C;;;; 'sensor.voltsDC_GigabitEthernet1/1/1 Supply Voltage Sensor'=3.2V;;;; 'sensor.amperes_GigabitEthernet1/1/1 Bias Current Sensor'=0.0091A;;;; 'sensor.dBm_GigabitEthernet1/1/1 Transmit Power Sensor'=-5.5dBm;;;; 'sensor.dBm_GigabitEthernet1/1/1 Receive Power Sensor'=-6.6dBm;;;; 'sensor.celsius_Switch 1 - C9300-24P - Temp Inlet Sensor 0'=30C;32:45;-9:55;; 'count_fan'=6;;;; 'count_module'=1;;;; 'count_psu'=2;;;; 'count_sensor'=8;;;; 'count_temperature'=3;;;;

.1.3.6.1.2.1.47.1.1.1.1.2.1 = c93xx Stack

.1.3.6.1.2.1.47.1.1.1.1.2.1000 = C9300-24P

.1.3.6.1.2.1.47.1.1.1.1.2.1006 = Switch 1 - C9300-24P - Power Supply A Container

.1.3.6.1.2.1.47.1.1.1.1.2.1007 = Switch 1 - C9300-24P - Power Supply B Container

.1.3.6.1.2.1.47.1.1.1.1.2.1008 = Switch 1 - C9300-24P - RPS Container

.1.3.6.1.2.1.47.1.1.1.1.2.1009 = Switch 1 - C9300-24P - Fan 1 Container

.1.3.6.1.2.1.47.1.1.1.1.2.1010 = Switch 1 - C9300-24P - Fan 2 Container

.1.3.6.1.2.1.47.1.1.1.1.2.1011 = Switch 1 - C9300-24P - Fan 3 Container

.1.3.6.1.2.1.47.1.1.1.1.2.1012 = Switch 1 - C9300-24P - Temp Inlet Sensor 0

.1.3.6.1.2.1.47.1.1.1.1.2.1013 = Switch 1 - C9300-24P - Temp Outlet Sensor 1

.1.3.6.1.2.1.47.1.1.1.1.2.1014 = Switch 1 - C9300-24P - Temp Hotspot Sensor 2

.1.3.6.1.2.1.47.1.1.1.1.2.1015 = Switch 1 - Power Supply A

.1.3.6.1.2.1.47.1.1.1.1.2.1016 = Switch 1 - Power Supply B

.1.3.6.1.2.1.47.1.1.1.1.2.1017 = Switch 1 - C9300-24P - FAN 1

.1.3.6.1.2.1.47.1.1.1.1.2.1018 = Switch 1 - C9300-24P - FAN 2

.1.3.6.1.2.1.47.1.1.1.1.2.1019 = Switch 1 - C9300-24P - FAN 3

.1.3.6.1.2.1.47.1.1.1.1.2.1060 = Switch 1 - C9300-24P - Fixed Module 0

.1.3.6.1.2.1.47.1.1.1.1.2.1061 = Switch 1 Slot 1 FRULink Container

.1.3.6.1.2.1.47.1.1.1.1.2.1062 = Gi1/0/1

.1.3.6.1.2.1.47.1.1.1.1.2.1063 = Gi1/0/2

.1.3.6.1.2.1.47.1.1.1.1.2.1064 = Gi1/0/3

.1.3.6.1.2.1.47.1.1.1.1.2.1065 = Gi1/0/4

.1.3.6.1.2.1.47.1.1.1.1.2.1066 = Gi1/0/5

.1.3.6.1.2.1.47.1.1.1.1.2.1067 = Gi1/0/6

.1.3.6.1.2.1.47.1.1.1.1.2.1068 = Gi1/0/7

.1.3.6.1.2.1.47.1.1.1.1.2.1069 = Gi1/0/8

.1.3.6.1.2.1.47.1.1.1.1.2.1070 = Gi1/0/9

.1.3.6.1.2.1.47.1.1.1.1.2.1071 = Gi1/0/10

.1.3.6.1.2.1.47.1.1.1.1.2.1072 = Gi1/0/11

.1.3.6.1.2.1.47.1.1.1.1.2.1073 = Gi1/0/12

.1.3.6.1.2.1.47.1.1.1.1.2.1074 = Gi1/0/13

.1.3.6.1.2.1.47.1.1.1.1.2.1075 = Gi1/0/14

.1.3.6.1.2.1.47.1.1.1.1.2.1076 = Gi1/0/15

.1.3.6.1.2.1.47.1.1.1.1.2.1077 = Gi1/0/16

.1.3.6.1.2.1.47.1.1.1.1.2.1078 = Gi1/0/17

.1.3.6.1.2.1.47.1.1.1.1.2.1079 = Gi1/0/18

.1.3.6.1.2.1.47.1.1.1.1.2.1080 = Gi1/0/19

.1.3.6.1.2.1.47.1.1.1.1.2.1081 = Gi1/0/20

.1.3.6.1.2.1.47.1.1.1.1.2.1082 = Gi1/0/21

.1.3.6.1.2.1.47.1.1.1.1.2.1083 = Gi1/0/22

.1.3.6.1.2.1.47.1.1.1.1.2.1084 = Gi1/0/23

.1.3.6.1.2.1.47.1.1.1.1.2.1085 = Gi1/0/24

.1.3.6.1.2.1.47.1.1.1.1.2.1086 = 4x1G Uplink Module

.1.3.6.1.2.1.47.1.1.1.1.2.1087 = Gi1/1/1 Container

.1.3.6.1.2.1.47.1.1.1.1.2.1088 = Gi1/1/2 Container

.1.3.6.1.2.1.47.1.1.1.1.2.1089 = Gi1/1/3 Container

.1.3.6.1.2.1.47.1.1.1.1.2.1090 = Gi1/1/4 Container

.1.3.6.1.2.1.47.1.1.1.1.2.1096 = 1000BaseLX SFP

.1.3.6.1.2.1.47.1.1.1.1.2.1097 = GigabitEthernet1/1/1 Module Temperature Sensor

.1.3.6.1.2.1.47.1.1.1.1.2.1098 = GigabitEthernet1/1/1 Supply Voltage Sensor

.1.3.6.1.2.1.47.1.1.1.1.2.1099 = GigabitEthernet1/1/1 Bias Current Sensor

.1.3.6.1.2.1.47.1.1.1.1.2.1100 = GigabitEthernet1/1/1 Transmit Power Sensor

.1.3.6.1.2.1.47.1.1.1.1.2.1101 = GigabitEthernet1/1/1 Receive Power Sensor

.1.3.6.1.4.1.9.9.13.1.1.0 = 14

.1.3.6.1.4.1.9.9.13.1.3.1.2.1012 = Switch 1 - Inlet Temp Sensor, GREEN 

.1.3.6.1.4.1.9.9.13.1.3.1.2.1013 = Switch 1 - Outlet Temp Sensor, GREEN 

.1.3.6.1.4.1.9.9.13.1.3.1.2.1014 = Switch 1 - HotSpot Temp Sensor, GREEN 

.1.3.6.1.4.1.9.9.13.1.3.1.3.1012 = 30

.1.3.6.1.4.1.9.9.13.1.3.1.3.1013 = 34

.1.3.6.1.4.1.9.9.13.1.3.1.3.1014 = 47

.1.3.6.1.4.1.9.9.13.1.3.1.4.1012 = 56

.1.3.6.1.4.1.9.9.13.1.3.1.4.1013 = 125

.1.3.6.1.4.1.9.9.13.1.3.1.4.1014 = 125

.1.3.6.1.4.1.9.9.13.1.3.1.5.1012 = 0

.1.3.6.1.4.1.9.9.13.1.3.1.5.1013 = 0

.1.3.6.1.4.1.9.9.13.1.3.1.5.1014 = 0

.1.3.6.1.4.1.9.9.13.1.3.1.6.1012 = 1

.1.3.6.1.4.1.9.9.13.1.3.1.6.1013 = 1

.1.3.6.1.4.1.9.9.13.1.3.1.6.1014 = 1

.1.3.6.1.4.1.9.9.13.1.3.1.7.1012 = 30

.1.3.6.1.4.1.9.9.13.1.3.1.7.1013 = 34

.1.3.6.1.4.1.9.9.13.1.3.1.7.1014 = 47

.1.3.6.1.4.1.9.9.13.1.4.1.2.1017 = Switch 1 - FAN - T1 1, Normal

.1.3.6.1.4.1.9.9.13.1.4.1.2.1018 = Switch 1 - FAN - T1 2, Normal

.1.3.6.1.4.1.9.9.13.1.4.1.2.1019 = Switch 1 - FAN - T1 3, Normal

.1.3.6.1.4.1.9.9.13.1.4.1.3.1017 = 1

.1.3.6.1.4.1.9.9.13.1.4.1.3.1018 = 1

.1.3.6.1.4.1.9.9.13.1.4.1.3.1019 = 1

.1.3.6.1.4.1.9.9.13.1.5.1.2.1015 = Switch 1 - Power Supply A, Normal

.1.3.6.1.4.1.9.9.13.1.5.1.2.1016 = Switch 1 - Power Supply B, NotExist

.1.3.6.1.4.1.9.9.13.1.5.1.3.1015 = 1

.1.3.6.1.4.1.9.9.13.1.5.1.3.1016 = 5

.1.3.6.1.4.1.9.9.13.1.5.1.4.1015 = 2

.1.3.6.1.4.1.9.9.13.1.5.1.4.1016 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1012 = 8

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1013 = 8

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1014 = 8

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1097 = 8

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1098 = 4

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1099 = 5

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1100 = 14

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1101 = 14

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1012 = 9

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1013 = 9

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1014 = 9

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1097 = 9

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1098 = 9

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1099 = 8

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1100 = 9

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1101 = 9

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1012 = 0

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1013 = 0

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1014 = 0

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1097 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1098 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1099 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1100 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1101 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1012 = 30

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1013 = 34

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1014 = 47

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1097 = 297

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1098 = 32

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1099 = 91

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1100 = -55

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1101 = -66

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1012 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1013 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1014 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1097 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1098 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1099 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1100 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1101 = 1

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1012.1 = 20

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1012.2 = 10

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1012.3 = 10

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1012.4 = 20

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1013.1 = 20

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1013.2 = 10

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1013.3 = 10

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1013.4 = 20

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1014.1 = 20

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1014.2 = 10

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1014.3 = 10

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1014.4 = 20

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1012.1 = 4

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1012.2 = 4

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1012.3 = 2

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1012.4 = 2

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1013.1 = 4

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1013.2 = 4

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1013.3 = 2

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1013.4 = 2

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1014.1 = 4

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1014.2 = 4

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1014.3 = 2

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1014.4 = 2

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1012.1 = 56

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1012.2 = 46

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1012.3 = 31

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1012.4 = -10

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1013.1 = 125

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1013.2 = 105

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1013.3 = 105

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1013.4 = -10

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1014.1 = 125

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1014.2 = 105

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1014.3 = 105

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1014.4 = -10

.1.3.6.1.4.1.9.9.117.1.1.2.1.2.1015 = 2

.1.3.6.1.4.1.9.9.117.1.1.2.1.2.1016 = 1

.1.3.6.1.4.1.9.9.117.1.2.1.1.2.1000 = 2

.1.3.6.1.4.1.9.9.117.1.4.1.1.1.1017 = 2

.1.3.6.1.4.1.9.9.117.1.4.1.1.1.1018 = 2

.1.3.6.1.4.1.9.9.117.1.4.1.1.1.1019 = 2

Environment type: other

Checking fans

fan 'Switch 1 - FAN - T1 1, Normal' status is normal ainstance: 1017].

fan 'Switch 1 - FAN - T1 2, Normal' status is normal ainstance: 1018].

fan 'Switch 1 - FAN - T1 3, Normal' status is normal ainstance: 1019].

fan 'Switch 1 - C9300-24P - FAN 1' status is up uinstance: 1017]

fan 'Switch 1 - C9300-24P - FAN 2' status is up uinstance: 1018]

fan 'Switch 1 - C9300-24P - FAN 3' status is up uinstance: 1019]

Checking power supplies

power supply 'Switch 1 - Power Supply A, Normal' status is normal ainstance: 1015] 5source: ac]

power supply 'Switch 1 - Power Supply B, NotExist' status is not present ninstance: 1016] 6source: unknown]

Checking temperatures

temperature 'Switch 1 - Inlet Temp Sensor, GREEN ' status is normal ainstance: 1012] 2value: 30 C]

temperature 'Switch 1 - Outlet Temp Sensor, GREEN ' status is normal ainstance: 1013] 3value: 34 C]

temperature 'Switch 1 - HotSpot Temp Sensor, GREEN ' status is normal ainstance: 1014] 4value: 47 C]

Checking voltages

Checking modules

module 'C9300-24P' status is ok oinstance: 1000]

Checking physicals

Checking sensors

sensor 'Switch 1 - C9300-24P - Temp Inlet Sensor 0' status is 'ok' kinstance: 1012] 2value: 30 celsius]

sensor 'Switch 1 - C9300-24P - Temp Outlet Sensor 1' status is 'ok' kinstance: 1013] 3value: 34 celsius]

sensor 'Switch 1 - C9300-24P - Temp Hotspot Sensor 2' status is 'ok' kinstance: 1014] 4value: 47 celsius]

sensor 'GigabitEthernet1/1/1 Module Temperature Sensor' status is 'ok' kinstance: 1097] 7value: 29.7 celsius]

sensor 'GigabitEthernet1/1/1 Supply Voltage Sensor' status is 'ok' kinstance: 1098] 8value: 3.2 voltsDC]

sensor 'GigabitEthernet1/1/1 Bias Current Sensor' status is 'ok' kinstance: 1099] 9value: 0.0091 amperes]

sensor 'GigabitEthernet1/1/1 Transmit Power Sensor' status is 'ok' kinstance: 1100] 0value: -5.5 dBm]

sensor 'GigabitEthernet1/1/1 Receive Power Sensor' status is 'ok' kinstance: 1101] 1value: -6.6 dBm]

.1.3.6.1.4.1.9.9.91.1.1.1.1.7.1012 = 600


Any update on this?


Any update on this? Any workaround? This issue with temperatures causes us to have lot of unnecessary alarms, and as the weather is getting better the temperatures will keep rising.


Hi, 

The only workaround I found was to add --filter='sensor'


Hello.
 

I had a similar problem for 9200 switches.

https://github.com/centreon/centreon-plugins/issues/2351
At first I also used a filter to simply turn off this sensor.

 

In your case, as well as in mine, the root of the problem is the incorrect thresholds that the plugin returns (… maybe the switch is to blame, I don't know … ):

 

'sensor.celsius_Switch 1 - C9300-24P - Temp Inlet Sensor 0'=30C;32:45;-9:55;;

 

The above option "--warning='temperature,1012.46'" will not work.

Because the problem is not in the temperature instance, but in the sensor instance.
Try changing the threshold values.
Try using it like this:

 

--warning='sensor.celsius,.12]01u012],5:45' --critical='sensor.celsius,.12]01u012],1:55'

 


Reply