Question

Cisco switch temperature problem

  • 18 January 2024
  • 6 replies
  • 248 views

Badge +5

Hi,

 

I would like to know if there is a bug in the plugin, or I am doing something wrong.

I have a Cisco 9300 series switch and I monitor environment from there.

Currently it is showing:

WARNING: Sensor 'Switch 1 - C9300-48P - Temp Inlet Sensor 0/1012' is 31 C

Environment type: other
Checking fans
fan 'Switch 1 - FAN - T1 1, Normal' status is normal [instance: 1017].
fan 'Switch 1 - FAN - T1 2, Normal' status is normal [instance: 1018].
fan 'Switch 1 - FAN - T1 3, Normal' status is normal [instance: 1019].
fan 'Switch 1 - C9300-48P - FAN 1' status is up [instance: 1017]
fan 'Switch 1 - C9300-48P - FAN 2' status is up [instance: 1018]
fan 'Switch 1 - C9300-48P - FAN 3' status is up [instance: 1019]
Checking power supplies
power supply 'Switch 1 - Power Supply A, Normal' status is normal [instance: 1015] [source: ac]
power supply 'Switch 1 - Power Supply B, NotExist' status is not present [instance: 1016] [source: unknown]
Checking temperatures
temperature 'Switch 1 - Inlet Temp Sensor, GREEN ' status is normal [instance: 1012] [value: 31 C]
temperature 'Switch 1 - Outlet Temp Sensor, GREEN ' status is normal [instance: 1013] [value: 36 C]
temperature 'Switch 1 - HotSpot Temp Sensor, GREEN ' status is normal [instance: 1014] [value: 50 C]
Checking voltages
Checking modules
module 'C9300-48P' status is ok [instance: 1000]
Checking physicals
Checking sensors
sensor 'Switch 1 - C9300-48P - Temp Inlet Sensor 0' status is 'ok' [instance: 1012] [value: 31 celsius]
sensor 'Switch 1 - C9300-48P - Temp Outlet Sensor 1' status is 'ok' [instance: 1013] [value: 36 celsius]
sensor 'Switch 1 - C9300-48P - Temp Hotspot Sensor 2' status is 'ok' [instance: 1014] [value: 50 celsius]
sensor 'TenGigabitEthernet1/1/1 Module Temperature Sensor' status is 'ok' [instance: 1129] [value: 32.7 celsius]
sensor 'TenGigabitEthernet1/1/1 Supply Voltage Sensor' status is 'ok' [instance: 1130] [value: 3.3 voltsDC]
sensor 'TenGigabitEthernet1/1/1 Bias Current Sensor' status is 'ok' [instance: 1131] [value: 0.0252 amperes]
sensor 'TenGigabitEthernet1/1/1 Transmit Power Sensor' status is 'ok' [instance: 1132] [value: -2.9 dBm]
sensor 'TenGigabitEthernet1/1/1 Receive Power Sensor' status is 'ok' [instance: 1133] [value: -5.7 dBm]

My command is:

/usr/lib/nagios/plugins/centreon_plugins.pl --plugin network::cisco::standard::snmp::plugin --mode=environment --hostname=1.2.3.4 --snmp-version=2c --snmp-community=xxx --verbose --critical='sensor,1012,56' --warning='sensor,1012,46' --snmp-retries=3

Why is it still showing as warning? Should the warning and critical part syntax be something different than the above one?

 

 


6 replies

Userlevel 4
Badge +12

Hi,

Have you tried this?

--critical='temperature,1012,56' --warning='temperature,1012,46'

Badge +5

bash-5.1$ /usr/lib/centreon/plugins/centreon_cisco_standard_snmp.pl --plugin network::cisco::standard::snmp::plugin --mode=environment --hostname=1.3.3.2 --snmp-username=kkk --authpassphrase=btca --authprotocol=SHA --privpassphrase=GHcjc --privprotocol=AES --snmp-version=3 --verbose --critical='temperature,1010,56' --warning='temperature,1010,46'

WARNING: Sensor 'Switch 1 - C9200L-24P-4G - Temp Inlet Sensor 0/1010' is 26 C | 'temp_Switch 1 - Inlet Temp Sensor, GREEN '=26C;0:46;0:56;; 'temp_Switch 1 - Outlet Temp Sensor, GREEN '=30C;;~:125;; 'temp_Switch 1 - HotSpot Temp Sensor, GREEN '=39C;;~:125;; 'sensor.celsius_Switch 1 - C9200L-24P-4G - Temp Outlet Sensor 1'=30C;;-9:124;; 'sensor.celsius_Switch 1 - C9200L-24P-4G - Temp Hotspot Sensor 2'=39C;;-9:124;; 'sensor.celsius_GigabitEthernet1/1/1 Module Temperature Sensor'=27.3C;;;; 'sensor.voltsDC_GigabitEthernet1/1/1 Supply Voltage Sensor'=3.2V;;;; 'sensor.amperes_GigabitEthernet1/1/1 Bias Current Sensor'=0.0191A;;;; 'sensor.dBm_GigabitEthernet1/1/1 Transmit Power Sensor'=-6dBm;;;; 'sensor.dBm_GigabitEthernet1/1/1 Receive Power Sensor'=-6.9dBm;;;; 'sensor.celsius_GigabitEthernet1/1/2 Module Temperature Sensor'=28.1C;;;; 'sensor.voltsDC_GigabitEthernet1/1/2 Supply Voltage Sensor'=3.3V;;;; 'sensor.amperes_GigabitEthernet1/1/2 Bias Current Sensor'=0.0216A;;;; 'sensor.dBm_GigabitEthernet1/1/2 Transmit Power Sensor'=-5.9dBm;;;; 'sensor.dBm_GigabitEthernet1/1/2 Receive Power Sensor'=-7.3dBm;;;; 'sensor.celsius_GigabitEthernet1/1/3 Module Temperature Sensor'=28.1C;;;; 'sensor.voltsDC_GigabitEthernet1/1/3 Supply Voltage Sensor'=3.3V;;;; 'sensor.amperes_GigabitEthernet1/1/3 Bias Current Sensor'=0.0208A;;;; 'sensor.dBm_GigabitEthernet1/1/3 Transmit Power Sensor'=-5.7dBm;;;; 'sensor.dBm_GigabitEthernet1/1/3 Receive Power Sensor'=-5.8dBm;;;; 'sensor.celsius_GigabitEthernet1/1/4 Module Temperature Sensor'=27.9C;;;; 'sensor.voltsDC_GigabitEthernet1/1/4 Supply Voltage Sensor'=3.2V;;;; 'sensor.amperes_GigabitEthernet1/1/4 Bias Current Sensor'=0.0214A;;;; 'sensor.dBm_GigabitEthernet1/1/4 Transmit Power Sensor'=-5.8dBm;;;; 'sensor.dBm_GigabitEthernet1/1/4 Receive Power Sensor'=-7.1dBm;;;; 'sensor.celsius_Switch 1 - C9200L-24P-4G - Temp Inlet Sensor 0'=26C;32:45;-9:55;; 'count_fan'=4;;;; 'count_module'=1;;;; 'count_psu'=2;;;; 'count_sensor'=23;;;; 'count_temperature'=3;;;;

Environment type: other

Checking fans

fan 'Switch 1 - FAN - T1 1, Normal' status is normal [instance: 1015].

fan 'Switch 1 - FAN - T1 2, Normal' status is normal [instance: 1016].

fan 'Switch 1 - C9200L-24P-4G - FAN 1' status is up [instance: 1015]

fan 'Switch 1 - C9200L-24P-4G - FAN 2' status is up [instance: 1016]

Checking power supplies

power supply 'Switch 1 - Power Supply A, Normal' status is normal [instance: 1013] [source: ac]

power supply 'Switch 1 - Power Supply B, Normal' status is normal [instance: 1014] [source: ac]

Checking temperatures

temperature 'Switch 1 - Inlet Temp Sensor, GREEN ' status is normal [instance: 1010] [value: 26 C]

temperature 'Switch 1 - Outlet Temp Sensor, GREEN ' status is normal [instance: 1011] [value: 30 C]

temperature 'Switch 1 - HotSpot Temp Sensor, GREEN ' status is normal [instance: 1012] [value: 39 C]

Checking voltages

Checking modules

module 'C9200L-24P-4G' status is ok [instance: 1000]

Checking physicals

Checking sensors

sensor 'Switch 1 - C9200L-24P-4G - Temp Inlet Sensor 0' status is 'ok' [instance: 1010] [value: 26 celsius]

sensor 'Switch 1 - C9200L-24P-4G - Temp Outlet Sensor 1' status is 'ok' [instance: 1011] [value: 30 celsius]

sensor 'Switch 1 - C9200L-24P-4G - Temp Hotspot Sensor 2' status is 'ok' [instance: 1012] [value: 39 celsius]

sensor 'GigabitEthernet1/1/1 Module Temperature Sensor' status is 'ok' [instance: 1091] [value: 27.3 celsius]

sensor 'GigabitEthernet1/1/1 Supply Voltage Sensor' status is 'ok' [instance: 1092] [value: 3.2 voltsDC]

sensor 'GigabitEthernet1/1/1 Bias Current Sensor' status is 'ok' [instance: 1093] [value: 0.0191 amperes]

sensor 'GigabitEthernet1/1/1 Transmit Power Sensor' status is 'ok' [instance: 1094] [value: -6 dBm]

sensor 'GigabitEthernet1/1/1 Receive Power Sensor' status is 'ok' [instance: 1095] [value: -6.9 dBm]

sensor 'GigabitEthernet1/1/2 Module Temperature Sensor' status is 'ok' [instance: 1097] [value: 28.1 celsius]

sensor 'GigabitEthernet1/1/2 Supply Voltage Sensor' status is 'ok' [instance: 1098] [value: 3.3 voltsDC]

sensor 'GigabitEthernet1/1/2 Bias Current Sensor' status is 'ok' [instance: 1099] [value: 0.0216 amperes]

sensor 'GigabitEthernet1/1/2 Transmit Power Sensor' status is 'ok' [instance: 1100] [value: -5.9 dBm]

sensor 'GigabitEthernet1/1/2 Receive Power Sensor' status is 'ok' [instance: 1101] [value: -7.3 dBm]

sensor 'GigabitEthernet1/1/3 Module Temperature Sensor' status is 'ok' [instance: 1103] [value: 28.1 celsius]

sensor 'GigabitEthernet1/1/3 Supply Voltage Sensor' status is 'ok' [instance: 1104] [value: 3.3 voltsDC]

sensor 'GigabitEthernet1/1/3 Bias Current Sensor' status is 'ok' [instance: 1105] [value: 0.0208 amperes]

sensor 'GigabitEthernet1/1/3 Transmit Power Sensor' status is 'ok' [instance: 1106] [value: -5.7 dBm]

sensor 'GigabitEthernet1/1/3 Receive Power Sensor' status is 'ok' [instance: 1107] [value: -5.8 dBm]

sensor 'GigabitEthernet1/1/4 Module Temperature Sensor' status is 'ok' [instance: 1109] [value: 27.9 celsius]

sensor 'GigabitEthernet1/1/4 Supply Voltage Sensor' status is 'ok' [instance: 1110] [value: 3.2 voltsDC]

sensor 'GigabitEthernet1/1/4 Bias Current Sensor' status is 'ok' [instance: 1111] [value: 0.0214 amperes]

sensor 'GigabitEthernet1/1/4 Transmit Power Sensor' status is 'ok' [instance: 1112] [value: -5.8 dBm]

sensor 'GigabitEthernet1/1/4 Receive Power Sensor' status is 'ok' [instance: 1113] [value: -7.1 dBm]

Userlevel 4
Badge +12

Can you run the same command with the --debug option please?

Badge +5

bash-5.1$ /usr/lib/centreon/plugins/centreon_cisco_standard_snmp.pl --plugin network::cisco::standard::snmp::plugin --mode=environment --hostname=1.3.3.5 --snmp-version=2c --snmp-community='public' --verbose --snmp-retries=3 --critical='temperature,1012,56' --warning='temperature,1012,46' --debug

WARNING: Sensor 'Switch 1 - C9300-24P - Temp Inlet Sensor 0/1012' is 30 C | 'temp_Switch 1 - Inlet Temp Sensor, GREEN '=30C;0:46;0:56;; 'temp_Switch 1 - Outlet Temp Sensor, GREEN '=34C;;~:125;; 'temp_Switch 1 - HotSpot Temp Sensor, GREEN '=47C;;~:125;; 'sensor.celsius_Switch 1 - C9300-24P - Temp Outlet Sensor 1'=34C;;-9:124;; 'sensor.celsius_Switch 1 - C9300-24P - Temp Hotspot Sensor 2'=47C;;-9:124;; 'sensor.celsius_GigabitEthernet1/1/1 Module Temperature Sensor'=29.7C;;;; 'sensor.voltsDC_GigabitEthernet1/1/1 Supply Voltage Sensor'=3.2V;;;; 'sensor.amperes_GigabitEthernet1/1/1 Bias Current Sensor'=0.0091A;;;; 'sensor.dBm_GigabitEthernet1/1/1 Transmit Power Sensor'=-5.5dBm;;;; 'sensor.dBm_GigabitEthernet1/1/1 Receive Power Sensor'=-6.6dBm;;;; 'sensor.celsius_Switch 1 - C9300-24P - Temp Inlet Sensor 0'=30C;32:45;-9:55;; 'count_fan'=6;;;; 'count_module'=1;;;; 'count_psu'=2;;;; 'count_sensor'=8;;;; 'count_temperature'=3;;;;

.1.3.6.1.2.1.47.1.1.1.1.2.1 = c93xx Stack

.1.3.6.1.2.1.47.1.1.1.1.2.1000 = C9300-24P

.1.3.6.1.2.1.47.1.1.1.1.2.1006 = Switch 1 - C9300-24P - Power Supply A Container

.1.3.6.1.2.1.47.1.1.1.1.2.1007 = Switch 1 - C9300-24P - Power Supply B Container

.1.3.6.1.2.1.47.1.1.1.1.2.1008 = Switch 1 - C9300-24P - RPS Container

.1.3.6.1.2.1.47.1.1.1.1.2.1009 = Switch 1 - C9300-24P - Fan 1 Container

.1.3.6.1.2.1.47.1.1.1.1.2.1010 = Switch 1 - C9300-24P - Fan 2 Container

.1.3.6.1.2.1.47.1.1.1.1.2.1011 = Switch 1 - C9300-24P - Fan 3 Container

.1.3.6.1.2.1.47.1.1.1.1.2.1012 = Switch 1 - C9300-24P - Temp Inlet Sensor 0

.1.3.6.1.2.1.47.1.1.1.1.2.1013 = Switch 1 - C9300-24P - Temp Outlet Sensor 1

.1.3.6.1.2.1.47.1.1.1.1.2.1014 = Switch 1 - C9300-24P - Temp Hotspot Sensor 2

.1.3.6.1.2.1.47.1.1.1.1.2.1015 = Switch 1 - Power Supply A

.1.3.6.1.2.1.47.1.1.1.1.2.1016 = Switch 1 - Power Supply B

.1.3.6.1.2.1.47.1.1.1.1.2.1017 = Switch 1 - C9300-24P - FAN 1

.1.3.6.1.2.1.47.1.1.1.1.2.1018 = Switch 1 - C9300-24P - FAN 2

.1.3.6.1.2.1.47.1.1.1.1.2.1019 = Switch 1 - C9300-24P - FAN 3

.1.3.6.1.2.1.47.1.1.1.1.2.1060 = Switch 1 - C9300-24P - Fixed Module 0

.1.3.6.1.2.1.47.1.1.1.1.2.1061 = Switch 1 Slot 1 FRULink Container

.1.3.6.1.2.1.47.1.1.1.1.2.1062 = Gi1/0/1

.1.3.6.1.2.1.47.1.1.1.1.2.1063 = Gi1/0/2

.1.3.6.1.2.1.47.1.1.1.1.2.1064 = Gi1/0/3

.1.3.6.1.2.1.47.1.1.1.1.2.1065 = Gi1/0/4

.1.3.6.1.2.1.47.1.1.1.1.2.1066 = Gi1/0/5

.1.3.6.1.2.1.47.1.1.1.1.2.1067 = Gi1/0/6

.1.3.6.1.2.1.47.1.1.1.1.2.1068 = Gi1/0/7

.1.3.6.1.2.1.47.1.1.1.1.2.1069 = Gi1/0/8

.1.3.6.1.2.1.47.1.1.1.1.2.1070 = Gi1/0/9

.1.3.6.1.2.1.47.1.1.1.1.2.1071 = Gi1/0/10

.1.3.6.1.2.1.47.1.1.1.1.2.1072 = Gi1/0/11

.1.3.6.1.2.1.47.1.1.1.1.2.1073 = Gi1/0/12

.1.3.6.1.2.1.47.1.1.1.1.2.1074 = Gi1/0/13

.1.3.6.1.2.1.47.1.1.1.1.2.1075 = Gi1/0/14

.1.3.6.1.2.1.47.1.1.1.1.2.1076 = Gi1/0/15

.1.3.6.1.2.1.47.1.1.1.1.2.1077 = Gi1/0/16

.1.3.6.1.2.1.47.1.1.1.1.2.1078 = Gi1/0/17

.1.3.6.1.2.1.47.1.1.1.1.2.1079 = Gi1/0/18

.1.3.6.1.2.1.47.1.1.1.1.2.1080 = Gi1/0/19

.1.3.6.1.2.1.47.1.1.1.1.2.1081 = Gi1/0/20

.1.3.6.1.2.1.47.1.1.1.1.2.1082 = Gi1/0/21

.1.3.6.1.2.1.47.1.1.1.1.2.1083 = Gi1/0/22

.1.3.6.1.2.1.47.1.1.1.1.2.1084 = Gi1/0/23

.1.3.6.1.2.1.47.1.1.1.1.2.1085 = Gi1/0/24

.1.3.6.1.2.1.47.1.1.1.1.2.1086 = 4x1G Uplink Module

.1.3.6.1.2.1.47.1.1.1.1.2.1087 = Gi1/1/1 Container

.1.3.6.1.2.1.47.1.1.1.1.2.1088 = Gi1/1/2 Container

.1.3.6.1.2.1.47.1.1.1.1.2.1089 = Gi1/1/3 Container

.1.3.6.1.2.1.47.1.1.1.1.2.1090 = Gi1/1/4 Container

.1.3.6.1.2.1.47.1.1.1.1.2.1096 = 1000BaseLX SFP

.1.3.6.1.2.1.47.1.1.1.1.2.1097 = GigabitEthernet1/1/1 Module Temperature Sensor

.1.3.6.1.2.1.47.1.1.1.1.2.1098 = GigabitEthernet1/1/1 Supply Voltage Sensor

.1.3.6.1.2.1.47.1.1.1.1.2.1099 = GigabitEthernet1/1/1 Bias Current Sensor

.1.3.6.1.2.1.47.1.1.1.1.2.1100 = GigabitEthernet1/1/1 Transmit Power Sensor

.1.3.6.1.2.1.47.1.1.1.1.2.1101 = GigabitEthernet1/1/1 Receive Power Sensor

.1.3.6.1.4.1.9.9.13.1.1.0 = 14

.1.3.6.1.4.1.9.9.13.1.3.1.2.1012 = Switch 1 - Inlet Temp Sensor, GREEN 

.1.3.6.1.4.1.9.9.13.1.3.1.2.1013 = Switch 1 - Outlet Temp Sensor, GREEN 

.1.3.6.1.4.1.9.9.13.1.3.1.2.1014 = Switch 1 - HotSpot Temp Sensor, GREEN 

.1.3.6.1.4.1.9.9.13.1.3.1.3.1012 = 30

.1.3.6.1.4.1.9.9.13.1.3.1.3.1013 = 34

.1.3.6.1.4.1.9.9.13.1.3.1.3.1014 = 47

.1.3.6.1.4.1.9.9.13.1.3.1.4.1012 = 56

.1.3.6.1.4.1.9.9.13.1.3.1.4.1013 = 125

.1.3.6.1.4.1.9.9.13.1.3.1.4.1014 = 125

.1.3.6.1.4.1.9.9.13.1.3.1.5.1012 = 0

.1.3.6.1.4.1.9.9.13.1.3.1.5.1013 = 0

.1.3.6.1.4.1.9.9.13.1.3.1.5.1014 = 0

.1.3.6.1.4.1.9.9.13.1.3.1.6.1012 = 1

.1.3.6.1.4.1.9.9.13.1.3.1.6.1013 = 1

.1.3.6.1.4.1.9.9.13.1.3.1.6.1014 = 1

.1.3.6.1.4.1.9.9.13.1.3.1.7.1012 = 30

.1.3.6.1.4.1.9.9.13.1.3.1.7.1013 = 34

.1.3.6.1.4.1.9.9.13.1.3.1.7.1014 = 47

.1.3.6.1.4.1.9.9.13.1.4.1.2.1017 = Switch 1 - FAN - T1 1, Normal

.1.3.6.1.4.1.9.9.13.1.4.1.2.1018 = Switch 1 - FAN - T1 2, Normal

.1.3.6.1.4.1.9.9.13.1.4.1.2.1019 = Switch 1 - FAN - T1 3, Normal

.1.3.6.1.4.1.9.9.13.1.4.1.3.1017 = 1

.1.3.6.1.4.1.9.9.13.1.4.1.3.1018 = 1

.1.3.6.1.4.1.9.9.13.1.4.1.3.1019 = 1

.1.3.6.1.4.1.9.9.13.1.5.1.2.1015 = Switch 1 - Power Supply A, Normal

.1.3.6.1.4.1.9.9.13.1.5.1.2.1016 = Switch 1 - Power Supply B, NotExist

.1.3.6.1.4.1.9.9.13.1.5.1.3.1015 = 1

.1.3.6.1.4.1.9.9.13.1.5.1.3.1016 = 5

.1.3.6.1.4.1.9.9.13.1.5.1.4.1015 = 2

.1.3.6.1.4.1.9.9.13.1.5.1.4.1016 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1012 = 8

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1013 = 8

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1014 = 8

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1097 = 8

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1098 = 4

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1099 = 5

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1100 = 14

.1.3.6.1.4.1.9.9.91.1.1.1.1.1.1101 = 14

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1012 = 9

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1013 = 9

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1014 = 9

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1097 = 9

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1098 = 9

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1099 = 8

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1100 = 9

.1.3.6.1.4.1.9.9.91.1.1.1.1.2.1101 = 9

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1012 = 0

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1013 = 0

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1014 = 0

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1097 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1098 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1099 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1100 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.3.1101 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1012 = 30

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1013 = 34

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1014 = 47

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1097 = 297

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1098 = 32

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1099 = 91

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1100 = -55

.1.3.6.1.4.1.9.9.91.1.1.1.1.4.1101 = -66

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1012 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1013 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1014 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1097 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1098 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1099 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1100 = 1

.1.3.6.1.4.1.9.9.91.1.1.1.1.5.1101 = 1

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1012.1 = 20

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1012.2 = 10

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1012.3 = 10

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1012.4 = 20

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1013.1 = 20

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1013.2 = 10

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1013.3 = 10

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1013.4 = 20

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1014.1 = 20

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1014.2 = 10

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1014.3 = 10

.1.3.6.1.4.1.9.9.91.1.2.1.1.2.1014.4 = 20

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1012.1 = 4

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1012.2 = 4

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1012.3 = 2

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1012.4 = 2

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1013.1 = 4

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1013.2 = 4

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1013.3 = 2

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1013.4 = 2

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1014.1 = 4

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1014.2 = 4

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1014.3 = 2

.1.3.6.1.4.1.9.9.91.1.2.1.1.3.1014.4 = 2

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1012.1 = 56

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1012.2 = 46

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1012.3 = 31

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1012.4 = -10

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1013.1 = 125

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1013.2 = 105

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1013.3 = 105

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1013.4 = -10

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1014.1 = 125

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1014.2 = 105

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1014.3 = 105

.1.3.6.1.4.1.9.9.91.1.2.1.1.4.1014.4 = -10

.1.3.6.1.4.1.9.9.117.1.1.2.1.2.1015 = 2

.1.3.6.1.4.1.9.9.117.1.1.2.1.2.1016 = 1

.1.3.6.1.4.1.9.9.117.1.2.1.1.2.1000 = 2

.1.3.6.1.4.1.9.9.117.1.4.1.1.1.1017 = 2

.1.3.6.1.4.1.9.9.117.1.4.1.1.1.1018 = 2

.1.3.6.1.4.1.9.9.117.1.4.1.1.1.1019 = 2

Environment type: other

Checking fans

fan 'Switch 1 - FAN - T1 1, Normal' status is normal [instance: 1017].

fan 'Switch 1 - FAN - T1 2, Normal' status is normal [instance: 1018].

fan 'Switch 1 - FAN - T1 3, Normal' status is normal [instance: 1019].

fan 'Switch 1 - C9300-24P - FAN 1' status is up [instance: 1017]

fan 'Switch 1 - C9300-24P - FAN 2' status is up [instance: 1018]

fan 'Switch 1 - C9300-24P - FAN 3' status is up [instance: 1019]

Checking power supplies

power supply 'Switch 1 - Power Supply A, Normal' status is normal [instance: 1015] [source: ac]

power supply 'Switch 1 - Power Supply B, NotExist' status is not present [instance: 1016] [source: unknown]

Checking temperatures

temperature 'Switch 1 - Inlet Temp Sensor, GREEN ' status is normal [instance: 1012] [value: 30 C]

temperature 'Switch 1 - Outlet Temp Sensor, GREEN ' status is normal [instance: 1013] [value: 34 C]

temperature 'Switch 1 - HotSpot Temp Sensor, GREEN ' status is normal [instance: 1014] [value: 47 C]

Checking voltages

Checking modules

module 'C9300-24P' status is ok [instance: 1000]

Checking physicals

Checking sensors

sensor 'Switch 1 - C9300-24P - Temp Inlet Sensor 0' status is 'ok' [instance: 1012] [value: 30 celsius]

sensor 'Switch 1 - C9300-24P - Temp Outlet Sensor 1' status is 'ok' [instance: 1013] [value: 34 celsius]

sensor 'Switch 1 - C9300-24P - Temp Hotspot Sensor 2' status is 'ok' [instance: 1014] [value: 47 celsius]

sensor 'GigabitEthernet1/1/1 Module Temperature Sensor' status is 'ok' [instance: 1097] [value: 29.7 celsius]

sensor 'GigabitEthernet1/1/1 Supply Voltage Sensor' status is 'ok' [instance: 1098] [value: 3.2 voltsDC]

sensor 'GigabitEthernet1/1/1 Bias Current Sensor' status is 'ok' [instance: 1099] [value: 0.0091 amperes]

sensor 'GigabitEthernet1/1/1 Transmit Power Sensor' status is 'ok' [instance: 1100] [value: -5.5 dBm]

sensor 'GigabitEthernet1/1/1 Receive Power Sensor' status is 'ok' [instance: 1101] [value: -6.6 dBm]

.1.3.6.1.4.1.9.9.91.1.1.1.1.7.1012 = 600

Badge +5

Any update on this?

Badge +5

Any update on this? Any workaround? This issue with temperatures causes us to have lot of unnecessary alarms, and as the weather is getting better the temperatures will keep rising.

Reply